CFL Series – CIS

Cable Identification System: CFL CIS

After excavation, sometimes it is confusing to identify the right cable from bunch of similar appearance cables. Cable identification is very important for safety of field personnel – Cutting a wrong cable can be fatal. So, we require a Cable Identification System having current direction facility to identify the wanted cable.Cable Identification is the most critical and safety related sequence during all the procedure of cable fault location. The correct identification of a cable out of a bundle of cables, where most of them can be cables in service, has to be carried out not only carefully, but also by means of an instrument widely eliminating the possibility of human error or misinterpretation.The Cable Identification System, CFL CIS from SCOPE is the ultimate solution for identifying wanted cable from a bunch of cables in a trench, pit or cable rack. The SCOPE’s Cable Identification System CFL CIS is designed to fulfill these most important safety aspects.
  • User Friendly LED Indication for Right & Wrong Cable Identification from multiple cables
  • Flexible coil is thin, flexible for easy insertion between closely mounted conductors or where access is restricted and provided with locking facility for contact firmness
  • Two different ranges of pulse current which enables the accurate Cable Identification in all types power cables
  • 10 Stages Amplifier Setting for Better Signal Receiving
  • Operation Via both Mains Supply and Internal Li-Ion Rechargeable battery
  • Compact, Light Weight, water resistant and dust proof design
  • Belt arrangement for receiver to easy carrying
  • User friendly and simple operation

TECHNICAL DATA

Full Product Specifications

ParametersCFL CIS
Pulse Voltage55VDC / 36VDC
Pulse Current100A / 60A
Pulse Sequence30 pulses/ min, User configurable
Pulse Width72ms
Power Supply100 to 265 VAC 50/60Hz
Battery11.1 V Li-ion Rechargeable Battery
Operating Time6 Hours
Weight6 Kg approx.
Dimension339mm x 295mm x 152 mm
Environmental-20°C to +55 °C, 95% RH(Non-Condensing)

 

ParametersCFL CIS-R
Display TypeLED scale
Flexible Clamp150mm Diameter
Sensitivity100% at 31.25Ω loop resistance
Amplifier Setting10 stages
Battery11.1 V Li-ion Rechargeable Battery
Operating Time8 Hours
Weight0.7 Kg approx.
Dimension210mm x 124mm x 51 mm
Environmental-20°C to +55 °C, 95% RH(Non-Condensing)

Related Products

This is an ‘All in One’ solution for detection, analysis & localisation of partial discharges in the insulation of high-voltage Transformers, Cables, GIS, Generators and Motors.The PD Analyser is an extremely useful device for condition estimation of high-voltage insulation. This multi-purpose device is designed for
  • Partial discharge measuring in high-voltage insulation at a high noise level
  • PD detection & identtification of various types of defects for effective insulation condition estimation
Battery banks have become an inseparable part of uninterrupted or back-up power supply arrangements in various industries like Power, Telecom, IT etc. In substations the critical protection, control & communication systems run on battery power. Hence the reliability of these battery banks is crucial to ensure smooth operation of equipment which they are serving. The capacity of battery may get reduced significantly before the expected life span of battery due to various reasons. The only way to assess the continual health of battery banks is periodical maintenance inspection & testing. Conducting a discharge test on batteries is most effective way to check the battery capacity.SCOPE introduces BLUe Series Battery Loading Units; these are moveble instruments for controlled & monitored discharge of batteries. They are designed for integrated site discharge test, design & QC test and also for monitoring discharge process of battery bank with connected load. Each single autonomous unit having built-in display, keypad and wireless communication with computer makes it very easy to use. It comes in different configurations ranging from 12V to 380V discharge voltages and 50A to 300A discharge currents.Various options are available to control & monitor the discharge process. With the help of optional Cell Monitoring Unit – CellMon, voltage of each individual cell can be monitored & data sent to main BLUe unit and then from main unit to computer via wireless communication. Each BLUe unit is supplied with computer downloading & analysis software for real time monitoring of discharge process.
SCOPE’s Single Phase (TTRM 101 / TTRM 102) and Three Phase (TTRM 301 / TTRM 302), Transformer Turns Ratio Meters are rugged yet light weight and highly reliable instruments to measure turns ratio of transformers in live switchyards up to 765kV.TTRM is equally suitable for use on manufacturing shop floor and test laboratories. It can be used for testing of single / three phase power transformers (star or delta connected, with or without neutral), CTs and PTs.
TRM Series Winding Resistance Meters are designed for field testing as well as for factory testing of large rotating machines & transformers up to 1000MVA, 765kV class under live switchyard conditions. DC Winding Resistance values of highly inductive objects like transformers, generators, motor etc. are directly displayed. A backlit LCD with a user-friendly menu sets up the instrument for the test. These meters are protected against the back-emf offered by large inductive windings.